What to know
The touch calibration procedure for the eTOP500G/eTOP600 serie products with capacitive touch screen
can be allowed or not, depending on:
- the panel model,
- from where Calibration procedure is executed.
The table below shows the possible combinations for eTOP500G:
CALIBRATION BEHAVIOR |
507G/507MG BSP < 1.66.7 |
507G/507MG BSP >= 1.66.7 |
510G All BSP |
515G All BSP |
Calibration launched from System Settings in User Mode (Rotating Menu) | Touch calibration is NOT supported.
Calibration procedure can be executed but new calibration settings are not stored. |
Touch calibration is NOT supported.
Calibration procedure start and suddendly close. |
Touch calibration is supported | Touch calibration is supported. |
Calibration launched from System Settings in System Mode (Tap-Tap Rotating Menu) | Touch calibration is NOT supported.
Calibration procedure can be executed but new calibration settings are not stored. |
Touch calibration is NOT supported.
Calibration procedure start and suddendly close. |
Touch calibration is NOT supported.
Calibration procedure start and suddendly close. |
Touch calibration is NOT supported.
Calibration procedure start and suddendly close. |
The table below shows the possible combinations for eTOP600:
CALIBRATION BEHAVIOR |
605
All BSP |
607M
All BSP |
607M
All BSP |
610
All BSP |
Calibration launched from System Settings in User Mode (Rotating Menu) | Touch calibration is supported. | Touch calibration is NOT supported.
Calibration procedure start and suddendly close. |
Touch calibration is supported | Touch calibration is supported. |
Calibration launched from System Settings in System Mode (Tap-Tap Rotating Menu) | Touch calibration is NOT supported.
Calibration procedure can be executed but new calibration settings are not stored. |
Touch calibration is NOT supported.
Calibration procedure start and suddendly close. |
Touch calibration is NOT supported.
Calibration procedure start and suddendly close. |
Touch calibration is NOT supported.
Calibration procedure start and suddendly close |
Calibration procedure if supported, as per table above, can be executed only from Rotating Menu: System Settings in User Mode.
If JMobile Runtime is installed the rotating menu is reachable from context menu “Show system settings” voice, by selecting the apposite voice “Calibrate touch”.
If JMobile Runtime is not installed and Runtime Loader is showed, the rotating menu is reachable from “System Settings” button.
Apposite instructions on screen will guide you trough the touch calibration procedure.
Applies to
eTOP500G/600 serie operator panels